Electrical Specifications |
|
Continuous Power Rating |
|
100 kW AC |
|
Nominal DC Power Rating |
|
105 kW DC |
|
Nominal AC Voltage |
|
400 VAC three phase |
|
Nominal AC Frequency |
|
50 Hz |
|
Line Power Factor |
|
> 0.99 above 20% rated power |
|
Maximum AC Line Current |
|
164 amps AC |
|
AC Current Distortion |
|
< 3% THD at rated power |
|
Max. Open Circuit Voltage |
|
650 VDC |
|
Power Tracking Window Range |
|
300 to 600 VDC |
|
Max. DC Input Current |
|
319 amps DC |
|
Peak Inverter Efficiency |
|
95.5% (includes transformer) |
|
European Weighted Efficiency |
|
94.6% |
|
Standby Tare Losses |
|
93 watts |
|
General Specifications |
|
Ambient Temperature Range |
|
-10 °C to +45 °C |
|
Enclosure Environmental Rating |
|
IP21 |
|
Enclosure |
|
Rittal TS Series |
|
Weight |
|
955 kg |
|
Dimensions (H x W x D) |
|
196 x 120 x 60 cm |
|
Altitude |
|
up to 2000 m without de-rating |
|
Relative Humidity |
|
0 to 95% non-condensing |
|
Features & Options |
|
Cooling Method |
|
Forced convection cooling |
|
Protective Functions |
|
AC over / under voltage, AC over / under frequency, over temperature, AC and DC over current, DC over voltage |
|
User Display Standard |
|
LCD, 4-line, 20-characters with keypad |
|
Disconnects (AC & DC) |
|
Integral to inverter assembly |
|
Isolation Transformer |
|
Integral to inverter assembly |
|
Communications Software |
|
Graphical user interface software for real time communications and control |
|
Data Acqusition and Logging |
|
Adjustable |
|
Interfaces |
|
Telephone modem for remote monitoring and faults notification via modem, RS232 |
|
Approvals & Safety |
|
The GT100E is compliant to applicable European Directive and CE marked : |
|
EMC Directive: EN 50081-2, EN 50082-2; Low Voltage Directive: EN 50178 |
|
The GT100E complies with the requirements of VDEW |
|
The GT100E is approved by the TÜV Rheinland |
|
The GT100E complies with the requirements of the Royal Decret (RD1663/2000), Spain |
|
Note: Specifications subject to change without notice. |